6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • Profibus PA - climate compensated

36790-EN-130321

Linearization curve

Sensor-TAG

Displayed value

Display unit

Scaling

Current output

Unit of measurement

Language

The following safety-relevant data are not read out or written:

SIL

HART mode

7)

PIN

Application

Copy sensor data

Copy sensor data?

The reset function resets all parameters adjusted by the user to the

delivery status and the peak values to the actual values.

Reset

Select reset?

Reset
Basic adjustment
Peak value, measured value
Peak value, temperature

Basic adjustment

The "Reset" "Basic adjustment" resets the values of the following

menu items:

Menu section

Function

Reset value

Basic settings

Sensor address

126

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

0 s

Linearization

Linear

Sensor-TAG

Sensor

Display

Displayed value

PA-Out

Service

Additional PA value

Secondary Value 1

Reset

7)

With instruments with signal output 4 … 20 mA/HART