VEGA VEGABAR 54 Profibus PA - climate compensated User Manual

Page 53

Advertising
background image

53

10 Supplement

VEGABAR 54 • Profibus PA - climate compensated

36790-EN-130321

Ʋ Diameter approx.

8 mm (0.315 in)

Ʋ Colour

Blue

Cable entry/plug

15)

Ʋ External housing

– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

blind plug M20 x 1.5

or:

– 1␣x plug (depending on the version), 1␣x blind stopper

M20␣x␣1.5

Spring-loaded terminals for wire cross-

section up to

2.5 mm² (AWG 14)

Display and adjustment module
Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the sensor without cover IP 40

Material

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Voltage supply
Operating voltage

Ʋ Non-Ex instrument

9 … 32 V DC

Ʋ Ex-ia instrument

9 … 24 V DC

Ʋ Exd instrument

14 … 32 V DC

Operating voltage with illuminated display and adjustment module

Ʋ Non-Ex instrument

18 … 32 V DC

Ʋ Ex-ia instrument

18 … 24 V DC

Ʋ Exd instrument

18 … 32 V DC

Max. number of sensors on the DP/PA

segment coupler non-Ex/Ex

32/10

Electrical protective measures
Protection rating

Ʋ Housing, standard

IP 66/IP 67

16)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

17)

Ʋ Process component in IP 68 version IP 68 (25 bar)

15)

Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.

16)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

17)

Only with instruments with absolute pressure ranges.

Advertising