VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual

Page 46

Advertising
background image

46

6 Set up with the indicating and adjustment module

VEGAPULS 62 • 4 … 20 mA/HART - four-wire

36504-EN-121011

signal suppression, user-programmed linearization curve, measured

value memory as well as event memory remain untouched. The

linearization is set to linear.
False signal suppression: Deleting a previously created false signal

suppression. The false signal suppression created in the factory

remains active.
Peak values measured value: Resetting of the measured min. and

max. distances to the actual measured value.
The following table shows the default values of the instrument. De-

pending on the instrument version, not all menu items are available or

differently assigned:

Menu

Menu item

Default value

Setup

Measurement

loop name

Sensor

Medium

Liquid/Water
Bulk solids/Crushed stones, gravel

Applications

Storage tank
Silo

Vessel form

Vessel bottom, dished boiler end
Vessel top, dished boiler end

Vesell height/

Measuring range

Recommended measuring range, see

"Technical data" in the supplement

Min. adjustment

Recommended measuring range, see

"Technical data" in the supplement

Max. adjustment

0,000 m(d)

Damping

0.0 s

Current output

mode

4 … 20 mA, < 3.6 mA

Current output

Min./Max.

Min. current 3.8 mA, max. current

20.5 mA

Lock operation

Released

Display

Language

Like order

Displayed value

Distance

Display unit

m

Scaling size

Volume
l

Scaling

0.00 lin %, 0 l
100.00 lin %, 100 l

Backlight

Switched off