VEGA VEGABAR 53 Profibus PA User Manual
Page 47
47
10 Supplement
VEGABAR 53 • Profibus PA
36723-EN-130321
Ʋ Connection cable between transmitter
and external electronics housing with
IP 68 version
PUR
Ʋ Type label support on connection
cable
PE hard
Ʋ Connection cable with IP 68 1 bar
version
PE, PUR
Weight approx.
0.8 kg (1.764 lbs)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Dynamic behaviour output
Run-up time approx.
10 s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 26: Sudden change of the process variable. t
T
: dead time; t
A
: rise time; t
S
: jump response time
1 Process variable
2 Output signal
Dead time
≤ 150 ms
Rise time
≤ 100 ms (10 … 90 %)
Step response time
≤ 250 ms (ti: 0 s, 10 … 90 %)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
Ʋ Min.
-5 … +95 %
Ʋ Max.
-5 … +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
Ʋ zero
-5 … +95 %
Ʋ Span
-5 … +105 %