4 Mounting

VEGAPULS 62 • Foundation Fieldbus

36506-EN-121011

max. 50 mm (1.97"

)

1

2

3

Fig. 21: Mounting of the instrument with insulated vessels.
1 Electronics housing

2 Distance piece

3 Vessel insulation

For level measurements in concrete silos, the sensors are often

mounted in protective boxes. These boxes can be for example metal-

lic, closed subsurface enclosures.

1

2

Fig. 22: Mounting of the instrument in an subsurface enclosure
1 Subsurface enclosure

2 Concrete bottom

For this application, the minimal amounts of stray radiation from the

sensor can be reflected and strengthened by the walls of the subsur-

face enclosures. In the case of sensors with plastic housings, this can

lead to coupling disturbances. This can be avoided by using a sensor

with aluminium or stainless steel housing.

The short examples give you introductory information on the flow

measurement. Detailed planning information is available from flume

manufacturers and in special literature.

Installation in subsurface

enclosures

Flow measurement with

rectangular flume