6 Set up with the indicating and adjustment module

VEGAPULS 62 • Foundation Fieldbus

36506-EN-121011

required. Corresponding linearisation curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. By activating the appropriate curve, the

volume percentage of the vessel is displayed correctly. If the volume

should not be displayed in percent but e.g. in l or kg, a scaling can be

also set in the menu item "Display".

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:

Delivery status: Restoring the parameter settings at the time

of shipment from the factory. A created false signal suppression,

user-programmable linearization curve, measured value memory

as well as event memory will be deleted.

Basic settings: Resetting of the parameter settings incl. special

and laboratory parameters to the default values of the respective

instrument. Any created false signal suppression, user program-

mable linearization curve, measured value memory as well as

event memory will be deleted.

Setup: Resetting of the parameter settings to the default values of

the respective instrument . Order-related settings remain but are

not taken over into the current parameters. User-generated false

signal suppression, user-programmed linearization curve, meas-

ured value memory, echo curve memory as well as event memory

remain untouched. The linearization is set to linear.

False signal suppression: Deleting a previously created false

signal suppression. The false signal suppression created in the

factory remains active.

Peak values measured value: Resetting of the measured min.

and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 62:

Additional adjustments/

Reset