6 Set up with the indicating and adjustment module

VEGAPULS 66 • 4 … 20 mA/HART - two-wire

36519-EN-121011

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the

vessel is displayed correctly. If the volume should not be displayed in

percent but e.g. in l or kg, a scaling can be also set in the menu item

"Display".

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.
Caution:

Note the following if the instrument with corresponding approval is

used as part of an overfill protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer

linearly proportional to the level. This must be taken into consideration

by the user, particularly when setting the switching point on the level

switch.

With a reset, certain parameter adjustments carried out by the user

are reset.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-

ment from the factory incl. the order-specific settings. A created false

signal suppression, user-programmable linearization curve as well as

the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and

laboratory parameters to the default values of the respective instru-

ment. A created false signal suppression, user programmable lineari-

zation curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the

respective instrument in the menu item Setup. User-generated false

signal suppression, user-programmed linearization curve, measured

value memory as well as event memory remain untouched. The

linearization is set to linear.
False signal suppression: Deleting a previously created false signal

suppression. The false signal suppression created in the factory

remains active.

Additional adjustments

- Reset