VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire User Manual

Page 62

Advertising
background image

62

11 Supplement

VEGAPULS 66 • 4 … 20 mA/HART - two-wire

36519-EN-121011

3

4

2

1

Fig. 48: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

35 m (114.83 ft)

Recommended measuring range

Ʋ Flange DN 150, 6"

up to 15 m (49.21 ft)

Ʋ Flange DN 250, 10"

up to 20 m (65.62 ft)

Output variable
Output signal

4 … 20 mA/HART

Fulfilled HART specification

7.0

Signal resolution

0.3 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current

22 mA

Starting current

≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on

Load

see load diagram under Power supply

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7.0

1)

Ʋ PV (Primary Value)

Distance to the level

Ʋ SV (Secondary Value)

Level as percentage value

Ʋ TV (Third Value)

Linearised percentage value

Ʋ QV (Fourth Value)

Scaled measured value

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

1)

Default values, can be assigned individually

Advertising