6 Set up with the indicating and adjustment module

VEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire

36524-EN-121011

The "Echo curve" shows the signal strength of the echoes over the

measuring range in dB. The signal strength enables an evaluation of

the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see

menu "Additional settings") of the empty vessel with signal strength in

"dB" over the measuring range.

A comparison of echo curve and false signal suppression allows a

more accurate conclusion on measurement reliability. The selected

curve is continuously updated. With the [OK] key, a submenu with

zoom functions is opened:

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

With the function "Echo curve memory" the echo curve can be saved

at the time of setup. This is generally recommended; for using the As-

set Management functions it is absolutely necessary. If possible, the

curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-

tion echo curve can be displayed and used to recognize signal

changes over the operating time. In addition, the echo curve of the

setup can be also displayed in the echo curve window and compared

with the actual echo curve.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Diagnoses/Curve indica-

tion

Diagnostics/Echo curve

memory

Additional adjustments/

False signal suppression