5 exchanging the electronics module – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) standpipe ver. 4 … 20 mA_HART - four-wire User Manual
Page 39
39
9 Diagnosis, Asset Management and service
VEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire
36524-EN-121011
Error
Cause
Rectification
4 … 20 mA signal
not stable
– Level fluctua-
tions
– Set damping according to the
instrument via the indicating and
adjustment module or PACTware/
DTM
4 … 20 mA signal
missing
– Electrical con-
nection faulty
– Check connection according to
chapter "Connection steps" and
if necessary, correct according to
chapter "Wiring plan".
– Voltage supply
missing
– Check cables for breaks; repair if
necessary
– Operating volt-
age too low or
load resistance
too high
– Check, adapt if necessary
Current sig-
nal greater than
22 mA or less
than 3.6 mA
– Electronics
module in the
sensor defec-
tive
– Exchange the instrument or send it
in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on
seven days a week around the clock.
Since we offer this service worldwide, the support is in the English
language. The service itself is free of charge, the only costs involved
are the normal call charges.
9.5 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module
with respective Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
ics modules are adapted to the respective sensor and differ in signal
output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
•
In the factory
•
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
Reaction after fault recti-
fication
24 hour service hotline