Nominal measuring range

in bar/kPa

Nominal measuring

range in psig

Average temperature co-

efficient of the zero signal

and the output span, in

the compensated temper-

ature range 0 … +100 °C

(+32 … +212 °F), refer-

ence temperature 20 °C

(68 °F)

Average temperature co-

efficient of the zero signal

and the output span, out-

side the compensated

temperature range

0 … 150 psig

< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%

Thermal change of the current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 32: Thermal change, current output

Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital HART interface as well as to analogue current output 4 … 20 mA. Specifications

refer to the set span. Turn down (TD) is the relation nominal measuring range/set span.

Nominal measuring range in bar/kPa

Nominal measuring

range in psig

Long-term drift of the zero signal

0 … 0.2 bar/0 … 20 kPa

0 … 3 psig

< (1 % x TD)/year

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (1 % x TD)/year

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.25 % x TD)/year

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

< (0.25 % x TD)/year

0 … 5 bar/0 … 500 kPa

0 … 70 psig

< (0.1 % x TD)/year

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< (0.1 % x TD)/year

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

< (0.1 % x TD)/year

Ambient conditions
Ambient, storage and transport temperature

Ʋ Version with connection tube

-40 … +80 °C (-40 … +176 °F)

Ʋ Version with suspension cable FEP,

PUR

-20 … +80 °C (-4 … +176 °F)