VEGA VEGABAR 66 Profibus PA - climate compensated User Manual

Page 63

Advertising
background image

63

10 Supplement

VEGABAR 66 • Profibus PA - climate compensated

36792-EN-130321

– This module must be used if a value should not be used in the data telegram of the cyclical

data traffic (e.g. replacement of the temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Tip:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:

AI (PA-OUT)

Temperature

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Format

Value

IEEE-754-

Floating point value

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Floating point value

Temperature

(FB2)

IEEE-754-

Floating point value

Additional Cyclic

Value

Status

Status

(FB2)

Status

Status

Fig. 35: Telegram configuration example 1

Example 2 with pressure value and temperature value without additional cyclical value:

AI (PA-OUT)

Temperature

Free Place

Byte-No.

1

2

3

4

5

6

7

8

9

10

Format

Value

IEEE-754-

Floating point value

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Floating point value

Temperature

(FB2)

Status

Status

(FB2)

Fig. 36: Telegram configuration example 2

Example 3 with pressure value and additional cyclical value without temperature value:

AI (PA-OUT)

Free Place

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Fig. 37: Telegram configuration example 3