VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual

Page 66

Advertising
background image

66

11 Supplement

VEGAPULS 61 • 4 … 20 mA/HART - four-wire

36500-EN-121011

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

0

1 2

3

Fig. 52: Deviation under reference conditions - plastic horn antenna
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Reproducibility

≤ ±1 mm

Deviation with bulk solids

The values depend to a great extent on the application.

Binding specifications are thus not possible.

Variables influencing measurement accuracy
Specifications apply to the HART signal and the current output
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm

Additional deviation through strong, high

frequency electromagnetic fields acc. to

EN 61326

< ±50 mm

Specifications apply also to the current output
Temperature drift - Current output

±0.03 %/10 K relating to the 16 mA span max. ±0.3 %

Deviation on the current output by ana-

logue/digital conversion

< ±15 µA

Deviation on the current output due to

strong, high frequency electromagnetic

fields acc. to EN 61326

< ±150 µA

Characteristics and performance data
Measuring frequency

K-band (26 GHz technology)

Measuring cycle time

Ʋ Standard electronics approx.

450 ms

Ʋ Electronics with increased sensitivity

approx.

700 ms

Step response time

1)

≤ 3 s

Tracking speed of the measuring window

max.

1 m/min

1)

Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk

solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).