VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 37

Advertising
background image

37

6 Set up with the display and adjustment module

VEGAPULS 63 • Foundation Fieldbus

36514-EN-130228

specifications is always the seal surface of the thread or flange. By

means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-

cause the min./max. adjustment is always carried out without chang-

ing the product level. These settings can be made ahead of time

without the instrument having to be installed.

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Min. adjustment" and confirm

with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to

the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with

[OK].

2. Prepare the percentage value for editing with [OK] and set the

cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

Setup - Min. adjustment

Setup - Max. adjustment

Advertising