VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 58

Advertising
background image

58

11 Supplement

VEGAPULS 63 • Foundation Fieldbus

36514-EN-130228

3

4

2

1

Fig. 46: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Length antenna cone

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.8 ft)

Recommended measuring range

Ʋ Flange DN 50, 2"

up to 15 m (49.21 ft)

Ʋ Flange DN 80, 3"

up to 35 m (114.8 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Flange DN 50, 2"

up to 15 m (49.21 ft)

Flange DN 80, 3"

up to 35 m (114.8 ft)

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable

Channel Numbers

Ʋ Channel 1

Process value

Ʋ Channel 8

Electronics temperature

Ʋ Channel 9

Count rate

Transmission rate

31.25 Kbit/s

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex d instruments

16 mA, ±0.5 mA

Resolution, digital

> 1 mm (0.039 in)