4 Mounting

VEGAPULS 66 • Profibus PA

36521-EN-121011

4 Mounting

4.1 General instructions

With instruments with threaded process fitting, suitable tools must be

applied for tightening the hexagon.

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

Use the recommended cables (see chapter "Connecting to power

supply") and tighten the cable gland.
You can give your instrument additional protection against moisture

penetration by leading the connection cable downward in front of the

cable entry. Rain and condensation water can thus drain off. This ap-

plies mainly to outdoor mounting as well as installation in areas where

high humidity is expected (e.g. through cleaning processes) or on

cooled or heated vessels.

Make sure that all parts of the instrument exposed to the process, in

particular the active measuring component, process seal and process

fitting, are suitable for the existing process conditions. These include

above all the process pressure, process temperature as well as the

chemical properties of the medium.
You can find the specifications in chapter "Technical data" and on the

type label.

4.2 Instructions for installation

The emitted radar impulses of the radar sensor are electromagnetic

waves. The polarisation plane is the direction of the electrical wave

component. By turning the instrument in the connection flange or

mounting boss, the polarisation can be used to reduce the effects of

false echoes.
The position of the polarisation plane is marked on the process fitting

of the instrument.

1

2

Fig. 5: Position of the polarisation level
1 Marking with version with horn antenna

2 Marking with version without horn antenna

When mounting the VEGAPULS 66, keep a distance of at least

500 mm (19.69 in) to the vessel wall. If the sensor is installed in the

Screwing in

Moisture

Suitability for the process

conditions

Polarisation plane

Installation position