6 Set up with the indicating and adjustment module
VEGAPULS 66 • Profibus PA
36521-EN-121011
•
Delivery status: Restoring the parameter settings at the time of
shipment from the factory incl. the order-specific settings. A cre-
ated false signal suppression, user-programmable linearization
curve, measured value memory as well as event memory will be
deleted.
•
Basic settings: Resetting of the parameter settings incl. special
and laboratory parameters to the default values of the respective
instrument. Any created false signal suppression, user program-
mable linearization curve, measured value memory as well as
event memory will be deleted.
•
Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
•
False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
•
Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 66:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Applications
Storage tank
Silo
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"Technical data" in the supplement
Min. adjustment
Recommended measuring range, see
"Technical data" in the supplement
Max. adjustment
0,000 m(d)
AI FB1 Channnel PV (lin. perc.)
AI FB1 scaling
unit
Height
%
AI FB1 scaling
0.00 lin %, 0.00 %
100.00 lin %, 100.00 %
AI FB1 damping
0 s
Lock operation
Released