4 Mounting

VEGABAR 82 • Slave sensor for electronic differential pressure

45050-EN-131011

1

2

Fig. 13: Measurement setup for differential pressure measurement of gases in

pipelines
1 VEGABAR 82

1 VEGABAR 82 - Slave sensor

4.6 Interface measurement

The master/slave combination is suitable for interface measurement

Requirements for a functioning measurement are:

Vessel with changing level

Products with steady densities

Interface always between the measurement points

Total level always above the upper measurement point

h

1,0

0,8

1

2

Fig. 14: Measurement setup with interface measurement, h = distance between

the two measuring points
1 VEGABAR 82

2 VEGABAR 82 - Slave sensor

Measurement setup