3 function chart "point level, 4 function chart, two-point control – VEGA VEGATOR 122 User Manual
Page 15
15
6 Setup
VEGATOR 122 •
46108-EN-131217
Note:
Keep in mind that downstream connected devices are activated dur-
ing the function test. This allows you to check the correct function of
the measuring system.
6.3 Function chart "Point level"
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
Note:
The switching conditions in the tables are only valid if the mode
switch on the sensor is set to "Max.".
Sensor
Signal conditioning instrument
Level
Sensor cur-
rent
LED yellow
(output)
LED red (fail-
ure)
Relay
approx. 8 mA
ON
approx. 16 mA
OFF
any
< 0.35 mA
> 6.8 mA
OFF
Sensor
Signal conditioning instrument
Level
Sensor cur-
rent
LED yellow
(output)
LED red (fail-
ure)
Relay
approx. 16 mA
ON
approx. 8 mA
OFF
any
< 3.6 mA
> 21 mA
OFF
6.4 Function chart, two-point control
The following charts provide an overview of the switching conditions
depending on the set mode and the level.
Overfill protection, point
level
Dry run protection, point
level