6 Functional safety (SIL)

FIBERTRAC 31 • 4 … 20 mA/HART - four-wire

43386-EN-131119

correctly. If necessary, other measures must be taken to maintain the

safety function.

All parameters changed by the operator are marked automatically so

that they can verified in the next step.

For the verification the PIN must be entered first and a comparison of

two character strings must be carried out. The user must confirm that

both character strings are identical, this is used to check the charac-

ter representation and the communication channels. The verification

texts are provided in German and with all other menu languages in

English.
In a second step, all modified, safety-relevant parameters are listed,

which must all be confirmed. After this process is finished, the instru-

ment will be locked automatically and the safety function is guaran-

teed again.

Warning:

If the described process was not carried out completely or correctly

(e.g. interruption or voltage loss), the instrument remains in the

released and hence unsafe status.

Warning:

In case of a reset to basic settings, all safety-relevant parameters will

also be reset to default. Therefore all safety-relevant parameters must

be checked or readjusted.

Change parameter

Verify parameters/Lock

adjustment

Incomplete process

Instrument reset