VEGA FIBERTRAC 31 4 … 20 mA_HART - four-wire With SIL qualification User Manual

Page 53

Advertising
background image

53

7 Set up with the display and adjustment module

FIBERTRAC 31 • 4 … 20 mA/HART - four-wire

43386-EN-131119

the adjustment of the sensor with full status (covered) and with empty

status (uncovered).
Hence, you will get a very reliable switching point.
With single point adjustment, you have to define the difference

between the min. and max. adjustment points (Delta I) yourself during

the following setup.

This menu item appears only if you have selected "Single point

adjustment" as adjustment mode (Setup/Adjustment mode).
In this menu item you determine the point at which the FIBERTRAC

31 should switch in uncovered status.
Empty the vessel until the sensor is uncovered.
For this enter the requested pulse rate manually or let the rate be

determined by FIBERTRAC 31. Automatic determination of the pulse

rate should be given preference.
The pulse rate is entered in ct/s. This is the number of counts per

second, i.e. the measured gamma radiation reaching the sensor.
Prerequisites:

Radiation is switched on - Source container is set to "ON"

There is no medium between source container and sensor

You can enter the value for "Adjustment uncovered" (ct/s) manually.

You can have the value for "Adjustment uncovered" determined by

FIBERTRAC 31.

This menu item appears only if you have selected "Single point

adjustment" as adjustment mode (Setup/Adjustment mode).
In this menu item you can adjust at which percentage value of the

max. pulse rate the sensor should switch over.
Since in most cases the radiation is almost completely absorbed

when the sensor is covered, the pulse rate when the sensor is cov-

ered is very low.

Setup/Adjustment

uncovered (single point

adjustment)

Setup/Delta I (single

point adjustment)