VEGA VEGAFLEX 86 Profibus PA Coax probe User Manual

Page 36

Advertising
background image

36

6 Set up with the display and adjustment module

VEGAFLEX 86 • Profibus PA

44229-EN-130910

You can enter the dielectric constant of the upper medium directly or

have the value determined by the instrument. To do this you have to

enter the measured or known distance to the interface.

In this menu item you can enter the max. adjustment for the level. With

interface measurement this is the maximum total level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

In this menu item you can enter the min. adjustment for the level. With

interface measurement this is the minimum total level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Setup - Max. adjustment

Level

Setup - Min. adjustment

Level

Advertising