VEGA VEGAFLEX 82 Foundation Fieldbus User Manual

Page 34

Advertising
background image

34

6 Set up with the display and adjustment module

VEGAFLEX 82 • Foundation Fieldbus

44221-EN-130910

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

In this menu item, you can enter the min. adjustment for the level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Deflectors, etc.

Note:

A false signal suppression is only recommended with liquid applica-

tions.
A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the lowest possible level so that all potential

interfering reflections can be detected.
Proceed as follows:

Setup - Min. adjustment

Level

Setup - False signal sup-

pression

Advertising