Input variable
Measured variable
The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.
3
4
2
1
Fig. 47: Data of the input variable
1
Reference plane
2
Measured variable, max. measuring range
3
Antenna length
4
Useful measuring range
Max. measuring range
35 m (114.83 ft)
Output variable
Output
-
Signal
digital output signal, Foundation Fieldbus protocol
-
Physical layer
according to IEC 61158-2
Damping (63 % of the input variable)
0 … 999 s, adjustable
Channel Numbers
-
Channel 1
Primary value
-
Channel 2
Secondary value 1
-
Channel 3
Secondary value 2
Transmission rate
31.25 Kbit/s
Current value
-
Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
-
Ex d instruments
16 mA, ±0.5 mA
Resolution, digital
> 1
mm (0.039 in)
VEGAPULS
62 • Approval according to LPR radio standard
65