6 exchanging the electronics module – VEGA VEGABAR 86 HART and accumulator pack - Operating Instructions User Manual

Page 44

Advertising
background image

44

8 Diagnosis, asset management and service

VEGABAR 86 • HART and accumulator pack

45040-EN-131107

F

T

: Thermal change of zero signal and output span

F

Kl

: Deviation

F

a

: Thermal change of the current output

You can find the specifications in chapter "Technical data".

Level measurement 1500 mmWs
Product temperature up to 40 °C
VEGABAR 86 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation ΔT: ΔT = 40 °C - 20 °C = 20 K
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.1 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.1 %)

2

)

F

perf

= 0.21 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.4)

F

stab

= 0.07 %

F

total

= 0.21 % + 0.07 % = 0.28 %

1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.1 %

F

a

= 0.15 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.1 %)

2

+ (0.15 %)

2

)

F

perf

= 0.25 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.4)

F

stab

= 0.07 %

F

total

= 0.25 % + 0.07 % = 0.32 %

8.6 Exchanging the electronics module

In case of a defect, the user can replace the electronics module with

another one of identical type.

Practical example

Calculation - Digital out-

put signal

Calculation - Analogue

output signal

Advertising