6 Set up with the display and adjustment module

VEGABAR 87 • 4 … 20 mA

45507-EN-131010

If with the automatic position correction, the actual measured value

should be taken over as corrective value, then this value must not be

influeces by product covering or a static pressure.
With the manual position correction, the offset value can be deter-

mined by the user. Select for this purpose the function "Edit" and

enter the requested value.
Save your settings with [OK] and move with [ESC] and [->] to the

next menu item.
When the position correction was carried out, then the actual meas-

ured value is corrected to 0. The corrective value appears with inverse

signs as offset value in the display.
The position correction can be repeated as often as necessary. How-

ever, if the sum of the corrective values exceeds 20 % of the nominal

measuring range, then no position correction is possible.

VEGABAR 87 always measures pressure independently of the pro-

cess variable selected in the menu item "Application". To output the

selected process variable correctly, an allocation to 0 % and 100 % of

the output signal must be carried out (adjustment).
During adjustment, the pressure is entered e.g. for the level with full

and empty vessel, see following example:

Parameterization example