VEGA VEGABAR 87 4 … 20 mA - Operating Instructions User Manual

Page 57

Advertising
background image

57

11 Supplement

VEGABAR 87 • 4 … 20 mA

45507-EN-131010

Accuracy class

Non-linearity, hysteresis and re-

peatability with TD 1 : 1 up to 5 : 1

Non-linearity, hysteresis and re-

peatability with 5 : 1

0.1 %

< 0.1 %

< 0.02 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
The thermal change of zero signal and output span corresponds to the value F

T

in chapter "Calcu-

lation of the total deviation (according to DIN 16086)".
Ceramic/Metal measuring cell - Standard

Medium or ambient temperature T
-40 … 0 °C (-40 … +32 °F)

< {0.15 % + 0.015 %/K x (-T)} x {0.5+0.5 x TD}

0 … +40 °C (+32 … +104 °F)

< {0.0075 %/K x (T - 20 °C)} x {0.5+0.5 x TD}

+40 … +100 °C (+104 … +212 °F)

< {0.15 % } x {0.5+0.5 x TD}

+100 … +120 °C (+212 … +248 °F)

< {0.15 % + 0.005 %/K x (T - 100 °C)} x {0.5+0.5 x TD}

Ceramic/Metal measuring cell - climate-compensated
Compensated temperature range

0 … +100 °C (+32 … +212 °F)

Non-compensated temperature range

-40 … 0 °C (-40 … +32 °F), -100 … 130 °C

(212 … +276 °F)

Nominal measuring range in bar/

kPa

Nominal measuring

range in psig

In the compensated

temperature range

In the non-compen-

sated temperature

range

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< {0.05 % + 0.1 x

(0.5+0.5 x TD)}

< {0.1 % + 0.15 x

(0.5+0.5 x TD)}

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< {0.1 % + 0.2 x

(0.5+0.5 x TD)}

< {0.1 % + 0.3 x

(0.5+0.5 x TD)}

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< {0.15 % + 0.4 x

(0.5+0.5 x TD)}

< {0.15 % + 0.6 x

(0.5+0.5 x TD)}

Thermal change, current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

The thermal change of the current output corresponds to the value F

a

in chapter "Calculation of the

total deviation (according to DIN 16086)".