VEGA VEGAFLEX 83 Profibus PA PFA insulated User Manual

Page 59

Advertising
background image

59

7 Setup with PACTware

VEGAFLEX 83 • Profibus PA

44226-EN-130910

Adjustment for the level measurement

If you have selected level measurement in the previous menu, then

you can enter the values for the min. and max. adjustment. The value

to be entered refers to the distance from the sealing surface of the

process fitting (sensor reference plane) to the surface of the product.
Adjustment for the level and interface measurement

If you have selected interface measurement in the previous menu,

then you can enter the values for the min. and max. adjustment of

level and interface or accept the values of the level measurement. The

entered value refers to the distance from the sealing surface of the

process fitting (sensor reference plane) to the total level or interface.

Linearization is required if the measured value should be outputted

in proportion to the volume and not the level. The linearization acts

identically on the level and the interface measurement. You can find

further linearization types in the extended adjustment.
If you have a non-linear vessel, you can select here the respective

linearization curve.

Linear

Spherical tank

Horizontal cylindrical tank

You must enter the following vessel dimensions with non-linear condi-

tions:

Height of the socket h

Vessel height D

In this window you can adjust the output signal. When the function is

inactive, you can change the settings via the "Extended adjustment".
Scaling unit

In the menu item "Out Scale Unit (scaling unit)" you define the scaling

unit, for example volume in l for the specified channel (measured

value).
Scaling

In the menu items "Out Scale (min.)" and "Out Scale (max.)" you

define the scaling of the measured values for 0 % and 100 %.

These settings allow you to optimize the sensor. With them you can

compare a sounded distance with the indicated value and correct it, if

necessary.
Probe immersed in the liquid (covered)

Select whether or not the probe is immersed in the medium.
Measured distance to the medium

If the probe is immersed in the medium, you can enter here the meas-

ured distance to the medium.

Step 3

Adjustment

Step 4

Linearization

Step 5

Setting - AI FB1

Step 6

Sensor optimization

Advertising