3 set instrument address – VEGA POINTRAC 31 Profibus PA User Manual

Page 21

Advertising
background image

21

5 Connecting to power supply

POINTRAC 31 • Profibus PA

43835-EN-131119

5 6 7 8

2

3

4

1

2

+

( )

(-)

1

Fig. 11: Adjustment and connection compartment (Ex-ia) with instruments with

intrinsically safe current output
1 Terminals for Profibus PA

2 Contact pins for the display and adjustment module or interface adapter

3 Terminals for the external display and adjustment unit

4 Ground terminal

5.3 Set instrument address

An address must be assigned to each Profibus PA instrument. The

approved addresses are between 0 and 126. Each address must

only be assigned once in the Profibus PA network. The sensor is only

recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

The hardware addressing is effective if an address <126 is adjusted

with the address selection switches on the instrument. Hence the

software addressing is no longer effective, the adjusted hardware

address is valid.

Adjustment and connec-

tion compartment - In-

struments with intrinsi-

cally safe current output

Instrument address

Hardware addressing