6 Set up with the display and adjustment module

POINTRAC 31 • Profibus PA

43835-EN-131119

Here, you can retrieve the adjustment value of the sensor. This is the

percentage value of the max. pulse rate at which the sensor switches

over.
If you have carried out a single point adjustment, this is the entered

value. With a two-point adjustment, this is the calculated value.
The value is an indication for the reliability and reproducibility of the

switching point.
The greater the difference in the pulse rate between covered and

uncovered status, the greater the differential value (Delta I) and the

more reliable the measurement. The automatically calculated damp-

ing is also oriented around the Delta I value. The higher the value, the

lower the damping.
A Delta I value below 10 % is an indication for a critical measurement.

In this menu item you can simulate measured values via the current

output. This allows the signal path to be tested, e.g. through down-

stream indicating instruments or the input card of the control system.
Note:

To carry out a simulation with the display and adjustment module,

you have to switch on the simulation switch on the electronics module

(switch position 1).
You can find the rotary switch on the electronics module in the elec-

tronics and connection department (large cover).
You can simulate different values:

Pulse rate of the sensor

Switching function of the relay

Information:

10 minutes after the key was pressed for the last time, the simulation

is interrupted automatically. You can also interrupt the simulation with

the switch on the electronics module.

Diagnosis - Adjustment

data

Diagnosis - Simulation