6 Set up with the display and adjustment module

VEGAFLEX 83 • Modbus and Levelmaster protocol

41843-EN-130314

In menu item "Current output, adjustment" you can assign a respec-

tive measured value to the current output.

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

Since the HART variables are very extensive, the indication was

divided into two menu items.
In the menu "HART variables 1" you can have the first HART value PV

(primary value) and the second HART value SV (secondary value) of

the sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.

In the menu "HART variables 2" you can have the third HART value

TV (third value) and the fourth HART value QV (quarter value) of the

sensor displayed.
The values cannot be changed in the display and adjustment module.

To change these values, you have to use the adjustment software

PACTware.

Setup - Current output,

adjustment

Setup - Current output

Min./Max.

Setup - HART variables

(1)

Setup - HART variables

(2)