VEGA VEGAFLEX 83 Modbus and Levelmaster protocol Polished version User Manual

Page 70

Advertising
background image

70

11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41843-EN-130314

Torque for exchangeable rod probe (in

the process fitting)

4.5 Nm ±0.5 (3.32 lbf ft)

Torque for NPT cable glands and Conduit tubes

Ʋ Plastic housing

max. 10 Nm (7.376 lbf ft)

Ʋ Aluminium/Stainless steel housing

max. 50 Nm (36.88 lbf ft)

Input variable
Measured variable

Level of liquids

Min. dielectric constant of the medium

ε

r

≥ 1.6

2

4

5

3

1

Fig. 36: Measuring ranges - VEGAFLEX 83
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (see diagrams under Accuracy - grey section)

5 Lower dead band (see diagrams under Accuracy - grey section)

Output variable
Output

Ʋ Physical layer

Digital output signal according to standard EIA-485

Ʋ Bus specifications

Modbus Application Protocol V1.1b, Modbus over serial

line V1.02

Ʋ Protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

9.6 Kbit/s

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Advertising