7 dimensions, 6 scadapack, Wiring plan – VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 78: Parameter

Advertising
background image

78

11 Supplement

VEGAPULS 67 • Modbus and Levelmaster protocol

41369-EN-121011

11.6 ScadaPack

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

3

2

13

45

5

2

1

3
4

9

6
7
8

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

COM Part 3 (C3)

RS485

TXD-

TXD+

GND

Fig. 56: Connection of VEGAPULS 67 to RTU ScadaPack
1 VEGAPULS 67

2 RTU ScadaPack

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Floating Point

Input Register Base Number

30001

The basic number of the input registers is always added to the input register address of VEGAPULS

67.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.

11.7 Dimensions

The following dimensional drawings represent only an extract of all possible versions. Detailed

dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".