4 Mounting

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44231-EN-130823

Fig. 7: Mounting of the sensor with inflowing medium

The reference plane for the measuring range of the sensors is the

sealing surface of the thread or flange.
Keep in mind that a min. distance must be maintained below the refer-

ence plane and possibly also at the end of the probe - measurement

in these areas is not possible (dead band). These dead bands are

listed in chapter "Technical data". Keep in mind for the adjustment that

the default setting for the measuring range refers to water.

The process fitting must be sealed if there is gauge or low pressure in

the vessel. Before use, check if the seal material is resistant against

the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical

data" or on the type label of the sensor.

Instruments for a temperature range up to 280 °C or up to 450 °C

have a distance piece between process fitting and electronics hous-

ing. Ths distance piece is used for thermal decoupling of the electron-

ics against high process temperatures.
Information:

The distance piece must only be incorporated up to max. 50 mm (2 in)

in the vessel isolation. Only then, a reliable temperature decoupling is

guaranteed.

Measuring range

Pressure

Mounting in the vessel

insulation