2 communication profibus pa – VEGA VEGABAR 81 Profibus PA - Operating Instructions User Manual

Page 67

Advertising
background image

67

11 Supplement

VEGABAR 81 • Profibus PA

45020-EN-131107

11.2 Communication Profibus PA

Instrument master file

The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.

These data are, e.g. the permissible transmission rates as well as information on diagnostics values

and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-

cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-

ment in the configuration tool.

ID number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. Optionally to this

manufacturer-specific GSD file, PNO provides also a general so-called profile-specific GSD file. If

the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM

software. By default, the sensor operates with the manufacturer-specific ID number. When using the

instruments on a segment coupler SK-2 or SK-3, no special GSD files are required.

Module of the PA sensors

For the cyclic data traffic, VEGABAR 81 provides the following modules:

AI FB1 (OUT)

– Out value of the AI FB1 after scaling

AI FB2 (OUT)

– Out value of the AI FB2 after scaling

AI FB3 (OUT)

– Out value of the AI FB3 after scaling

Free Place

– This module must be used if a value in the data telegram of the cyclical data traffic should not

be used (e.g. replacement of temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1

AI FB1 (OUT)

AI FB2 (OUT)

AI FB3 (OUT)

Advertising