11 Supplement

POINTRAC 31 • Foundation Fieldbus

41779-EN-131119

Electrical protective measures
Protection, depending on housing ver-

sion

IP 66/IP 67

4)

Overvoltage category

III

Protection class

I

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.

They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as

well as under "Downloads" and "Approvals".

11.2 Supplementary information Foundation Fieldbus

The following table gives you an overview of the instrument versions and the corresponding device

descriptions, the electrical characteristics of the bus system as well as the applied function blocks.

Revisions Data

DD-Revision

Rev_01

CFF-File

010101.cff

Device Revision

0101.ffo
0101.sym

Cff-Revision

xx xx 01

Device software revision

> 1.5.0

ITK (Interoperability Test Kit) Number

6.0.1

Electricial Characteristics

Physicial Layer Type

Low-power signaling, bus-pow-

ered, FISCO I.S.

Input Impedance

> 3000 Ohms between 7.8 KHz -

39 KHz

Unbalanced Capacitance

< 250 pF to ground from either in-

put terminal

Output Amplitude

0.8 V P-P

Electrical Connection

4 Wire

Polarity Insensitive

Yes

Max. Current Load

10 mA

Device minimum operating voltage

9 V

Transmitter Function Blocks

Resource Block (RB)

1

Transducer Block (TB)

1

Standard Block (AI)

3

Execution Time

30 ms

Diagnostics

Standard

Yes

Advanced

Yes

Performance

No

Function Blocks Instantiable

No

4)

A suitable cable is the prerequisite for maintaining the protection rating.