4 rectify faults, Level time 0 – VEGA VEGAFLEX 83 Foundation Fieldbus PFA insulated User Manual

Page 62

Advertising
background image

62

9 Diagnostics and service

VEGAFLEX 83 • Foundation Fieldbus

44227-EN-130910

Code
Text mes-

sage

Cause

Rectification

M505
No echo avail-

able

– Level echo can no longer

be detected

– Clean the antenna

– Use a more suitable

antenna/sensor

– Remove possible false

echoes

– Optimize sensor position

and orientation

9.4 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measures are:

Evaluation of fault messages, for example via the display and

adjustment module

Checking the output signal

Treatment of measurement errors

Further comprehensive diagnostics options offer a PC with the soft-

ware PACTware and the suitable DTM. In many cases, the reasons

can be determined in this way and faults can be rectified.

The below tables show typical examples for application-relevant

measurement errors. There are two measurement errors:

Constant level

Filling

Emptying

The images in column "Error pattern" show the real level with a bro-

ken line and the level displayed by the sensor as a continuous line.

1
2

Level

time

0

Fig. 32: The broken line 1 shows the real level, the continuous line 2 shows the

level displayed by the sensor

Reaction when malfunc-

tions occur

Procedure for fault recti-

fication

Treatment of measure-

ment errors

Advertising