VEGA VEGABAR 81 4 … 20 mA_HART - Operating Instructions User Manual

Page 16

Advertising
background image

16

4 Mounting

VEGABAR 81 • 4 … 20 mA/HART

45018-EN-131010

2

1

3
4

3
4

Fig. 6: Position of the filter element - Ex-d version
1 Single chamber housing, aluminium, stainless steel precision casting

2 Double chamber housing, aluminium, stainless steel precision casting

3 Rotatable metal ring

4 Filter element

Instruments with absolute pressure have a blind plug mounted

instead of the filter element.

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

The process assembly of instruments with Second Line of Defense

(gastight leadthrough) is completely encapsulated. An absolute pres-

sure measuring cell is used so that no ventilation is required.

1

1

Fig. 7: Position of the filter element - gastight leadthrough
1 Filter element

With relative pressure measuring ranges, the ambient pressure is

detected and compensated by a reference sensor in the electronics.

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

Instruments with Second

Line of Defense

Instruments in IP 69K

version

Advertising