5 set instrument address – VEGA WEIGHTRAC 31 Profibus PA User Manual

Page 32

Advertising
background image

32

5 Connecting to power supply

WEIGHTRAC 31 • Profibus PA

43837-EN-131119

The digital tachometer is powered by WEIGHTRAC 31. When using

the digital tachometer, you must power WEIGHTRAC 31 with max.

24 V.
The following cable colors are valid if the tachometer is ordered with

cable.

2

1

16
15

A

1

1

24

56

22

11

12

21

22

19

20

18
17

14
13

16
15

12

91

01
1

Fig. 19: Belt speed - plant control system (PLC) or tachometer (analogue)
A Tachometer (digital)

1 Voltage supply - cable colour brown

2 Voltage supply - cable colour white

15 Digital input - cable colour green

16 Digital input - cable colour yellow

5.5 Set instrument address

An address must be assigned to each Profibus PA instrument. The

approved addresses are between 0 and 126. Each address must

only be assigned once in the Profibus PA network. The sensor is only

recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

The hardware addressing is effective if an address <126 is adjusted

with the address selection switches on the instrument. Hence the

software addressing is no longer effective, the adjusted hardware

address is valid.

Instrument address

Hardware addressing