VEGA WEIGHTRAC 31 Profibus PA User Manual

Page 54

Advertising
background image

54

7 Setup with PACTware

WEIGHTRAC 31 • Profibus PA

43837-EN-131119

Basic settings: Restores the parameter settings at the time of ship-

ment Ex factory including the order-specific settings. The measured

value memory is deleted.
Factory settings: Resets parameter settings including special

parameters to the default values of the respective instrument. The

measured value memory and the order-specific settings are deleted.
Peak values: Resets the parameter settings in the menu item "Setup"

to the default values of the respective instrument. Order-specific

settings remain but are not taken over into the current parameters.

The measured value memory as well as the event memory remain

unaffected.
The following table shows the default values of the instrument. The

values apply for the application "Mass flow". The application must be

selected first.
Depending on the instrument version, not all menu items may be

available or they may be differently assigned:

Setup

Menu item

Default value

Modified value

Sensor address

126

Measurement loop name Sensor
Isotope

Cs-137

Application

Mass flow

Unit - Belt/screw speed m/s
Speed

1 m/s

Background radiation

0 ct/s

Unit of the process value t/h
Adjustment max.

Max. process value:

999 t/h

Adjustment min.

Min. process value: 0 t/h

Actual zero rate

90000

Linearization

-

AI FB 1 Tag Descriptor

-

AI FB 1 Channel

Process value

AI FB 1 scaling

0 t/h = 0 %
100 t/h = 100 %

AI FB 1 Lin. Type

Linear

AI FB 1 Out Scale Unit

%

AI FB 1 Out Scale Deci-

mal Point

#.##

AI FB 1 damping

0 s

Advertising