6 Set up with the display and adjustment module

VEGAFLEX 81 • Profibus PA

44214-EN-130910

In menu item"Channel" you determine which measured value the

output refers to.

In menu item "Scaling unit" you define the scaling variable and the

scaling unit for the level value on the display, e.g. volume in l.

In menu item "Scaling" you define the scaling format on the display

and the scaling of the measured level values for 0 % and 100 %.

Level measured value min.

Measured level value max.

To damp process-dependent measured value fluctuations, you can

set a time of 0 … 999 s in this menu item.
The damping applies to the level and interface measurement.

The default setting is a damping of 0 s.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.

Setup - AI FB1 - Channel

Setup - AI FB1 - Scaling

unit

Setup - AI FB1 - Scaling

Setup - AI FB1 - Damping

Lock/release setup - Ad-

justment