Altronix AL1002ULADA Installation Instructions User Manual

Page 3

Advertising
background image

AL1002ULADA

- 3 -

Power Supply Specifications:

AC Input:

120VAC 60Hz, 5 amp.

Output:

Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current.
One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised
total output current must not exceed current 10 amp in Alarm Condition.

Battery:

Use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries connected in series.

Stand-by/Alarm Current
Consumption:

130mA/300mA

EOL Resistor
(end of line):

2.2K (2200 ohm), Altronix Model # AL-EOL22 (included).

Ground fault maximum
test impedance:

1000 ohm.

Stand-by Specifications:

Stand-by Batteries

Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output

24VDC/7AH

24 Hours

10 amp/5 minutes

---

24VDC/12AH
(use two (2) 12VDC batteries in series)

24 Hours

10 amp/5 minutes

50mA

24VDC/36AH

24 Hours

10 amp/5 minutes

1 amp

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power

outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When

loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total

alarm current (example: AUX = 1 amp, outputs up to 9 amp).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA
72/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.

Carefully review:
Application Guide for AL602ULADA, AL802ULADA, AL1002ULADA
Power Supply Specifications

(pg. 3)

Stand-by Specifications

(pg. 3)

Output Programming Selection Table

(pg. 4)

Sync Mode Selection Table

(pg. 4)

Terminal Identification Table

(pgs. 5-6)

LED Status Indication Table

(pg. 6)

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes.

Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over
the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 12).

2. Connect green lead to earth ground (Fig 1). Connect the line (L) and neutral (N) terminals to a separate unswitched

AC circuit (120VAC, 60Hz) dedicated to the Fire Alarm System.

3. Measure output voltage before connecting devices. This helps avoiding potential damage.

4. Connect battery to the terminals marked [+ BAT -- ] on the Power Supply Board (battery leads included).

Note: If batteries being used in your installation do not fit into the AL1002ULADA unit, it is required to install a

separate enclosure, UL Listed for appropriate application. Separate battery enclosure is required to have 50 cubic inches
of additional open space. All wiring methods shall be in accordance with the National Electrical Code NFPA 70/

NFPA 72/ANSI and with all local codes and authorities having jurisdiction. Battery circuits are not power-limited;
provide 0.25” spacing from power-limited circuits and use separate knockout. If additional battery enclosure
is required, it must be UL Listed for the application and mounted within 5’ of the AL1002ULADA enclosure in the
same room; minimum 12 AWG wire in appropriate conduit is required for connection. When using conduit, make
sure it is installed in a matter where it can not turn.

5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and

desired output signal type (Output Programming Selection Table, pg. 4).

L N

line

ground

neutral

Fig. 1

Advertising