Altronix AL1002ULADA Installation Instructions User Manual

Page 9

Advertising
background image

AL1002ULADA

- 9 -

Battery Calculation Worksheet

Device

Number of

Devices

Current per Device

Stand-by

Current

Alarm
Current

For each device use this formula: This column x This column = Equals

Current per number of devices.

AL1002ULADA
(Current draw from battery)

1

Stand-by:

130mA

130mA

Alarm:

300mA

300mA

A

AL1002 Current

130mA

300mA

Auxiliary Devices

Refer to device manual for current ratings.

Alarm/Stand-by

mA

mA

mA

Alarm/Stand-by

mA

mA

mA

Alarm/Stand-by

mA

mA

mA

B

Auxiliary Devices Current (must not exceed 1 amp)

Refer to device manual for current ratings.

Alarm:

mA

0mA

mA

Alarm:

mA

0mA

mA

Alarm:

mA

0mA

mA

Alarm:

mA

0mA

mA

C Notification Appliances Current must not exceed 10 amp (10,000mA) 0mA

mA

D Total alarm current

mA

mA

E Total current ratings converted to amperes (line D x 0.001)

A

A

F Number of stand-by hours (24 for NFPA 72, Chapter 1, 1-5.2.5).

H

G Multiply lines E and F.

Total stand-by AH

AH

H

Alarm sounding period in hours.
(For example, 5 minutes = .0833 hours.)

H

I Multiply lines E and H.

Total alarm AH

AH

J Add lines G and I.

Total stand-by and alarm AH

AH

K

Multiply line J by 1.30.
(30% extra insurance to meet desired performance)
Total ampere - hours required

AH

Units are capable of recharging 36AH battery max. If total ampere - hour required exceeds 36AH,
decrease AUX current to provide enough stand-by time for the application.