PM50B4L1C060
Photo Voltaic IPM
H-Bridge
50 Amperes/600 Volts

Powerex, Inc., 173 Pavilion Lane, Youngwood, Pennsylvania 15697 (724) 925-7272 www.pwrx.com

3

03/11 Rev. 0

Electrical and Mechanical Characteristics,

T

j

= 25°C unless otherwise specified

Characteristics

Symbol

Test Conditions

Min.

Typ.

Max.

Units

Inverter Part

Collector-Emitter Saturation Voltage

V

CE(sat)

V

D

= 15V, I

C

= 50A, V

CIN

= 0V,

2.2

2.7

Volts

Pulsed, T

j

= 25°C

V

D

= 15V, I

C

= 50A, V

CIN

= 0V,

2.2

2.7

Volts

Pulsed, T

j

= 125°C

Emitter-Collector Voltage

V

EC

I

E

= 50A, V

D

= 15V, V

CIN

= 15V

2.4

3.3

Volts

Switching Times

t

on

0.1

0.5

1.2

µs

t

rr

V

D

= 15V, V

CIN

= 0 ↔ 15V

— 0.1 0.2 µs

t

C(on)

V

CC

= 300V, I

C

= 50A,

0.15

0.3

µs

t

off

T

j

= 125°C, Inductive Load

1.1

2.0

µs

t

C(off)

0.2

0.4

µs

Collector-Emitter Cutoff Current

I

CES

V

CE

= V

CES

, V

D

= 15V, V

CIN

= 15V, T

j

= 25°C —

1.0

mA

V

CE

= V

CES

, V

D

= 15V,

10

mA

V

CIN

= 15V, T

j

= 125°C

Control Part

Circuit Current

I

D

V

D

= 15V, V

CIN

= 15V, V

N1

-V

NC

— 6.5 12 mA

V

D

= 15V, V

CIN

= 15V, V

*P1

-V

*PC

— 1.6 4 mA

Input ON Threshold Voltage

V

th(on)

Applied between U

P

-V

UPC

,

1.2 1.5 1.8 Volts

Input OFF Threshold Voltage

V

th(off)

V

P

-V

VPC

, U

N

- V

N

- W

N

-Br-V

NC

1.7 2.0 2.3 Volts

Short Circuit Trip Level

SC

-20°C ≤ T

j

≤ 125°C, V

D

= 15V

75

Amperes

Short Circuit Current Delay Time

t

off(SC)

V

D

= 15V

0.2

µs

Over Temperature Protection

OT

Trip Level

135

°C

(Detect Temperature of IGBT)

OT

(hys)

Hysteresis

— 20 — °C

Supply Circuit Under-voltage Protection

UV

t

Trip Level

11.5

12.0

12.5

Volts

(-20°C ≤ T

j

≤ 125°C)

UV

r

Reset

Level

— 12.5 — Volts

Fault Output Current

I

FO(H)

V

D

= 15V, V

FO

= 15V

0.01

mA

I

FO(L)

V

D

= 15V, V

FO

= 15V

10

15

mA

Fault Output Pulse Width*

2

t

FO

V

D

= 15V

1.0

1.8

ms

*2 Fault output is given only when the internal SC, OT and UV protections schemes of either upper or lower devide operate to protect it.
Fault output of SC protection given pulse. Fault output of OT, UV protection given pulse while over trip level.