C&H Technology TAK7--12 User Manual

Page 3

Advertising
background image

Powerex, Inc., 173 Pavilion Lane, Youngwood, Pennsylvania 15697 (724) 925-7272

Phase Control SCR

www.pwrx.com

1200 Amperes Average

4400 Volts

Revision Date: 03/26/2010

TAK7

1200A

®




Absolute Maximum Ratings

Characteristics Symbol

Units

Non-Repetitive Transient Peak Reverse Blocking Voltage

V

RSM

V

RRM

+ 100V

Volts

RMS On-State Current, T

C

= 82°C

I

T(RMS)

1700 Amperes

Average Current 180° Sine Wave, T

C

= 82°C

I

T(AV)

1200

Amperes

RMS On-State Current, T

C

= 55°C

I

T(RMS)

Amperes

Average Current 180° Sine Wave, T

C

= 55°C

I

T(AV)

960

Amperes

Peak One Cycle Surge On-State Current (Non-Repetitive) 60 Hz

I

TSM

40,000

Amperes

Peak One Cycle Surge On-State Current (Non-Repetitive) 50 Hz

I

TSM

36,500

Amperes

Critical Rate-of-rise of On-State Current (Non-Repetitive)

di/dt

400

A/μsec

Critical Rate-of-rise of On-State Current (Repetitive)

di/dt

150

A/μsec

I

2

t (for Fusing) for One Cycle, 60 Hz

I

2

t

6.67 X 10

6

A

2

sec

Peak Gate Power Dissipation

P

GM

16

Watts

Average Gate Power Dissipation

P

G(av)

3

Watts

Operating Temperature

T

J

-40 to +125

°C

Storage Temperature

T

stg

-40 to +150

°C

Approximate Weight

2.2

lb

1000

g

Mounting Force

9000 to 11000

lb.

4100 to 5000

kg.

























Information presented is based upon manufacturers testing and projected capabilities.
This information is subject to change without notice.
The manufacturer makes no claim as to the suitability of use, reliability, capability,
or future availability of this product.