Warning, Ae c, Ac e – Peerless-AV GC-PS3S - Installation User Manual

Page 4: Installation to solid concrete or cinder block, Figure. 1.4

Advertising
background image

4 of 7

ISSUED: 1-17-11 SHEET #: 125-9181-1

SOLID CONCRETE

CINDER BLOCK

Installation to Solid Concrete or Cinder Block

• When installing Peerless wall mounts on cinder block, verify that you have a minimum of 1-3/8" (35 mm) of actual con-

crete thickness in the hole to be used for the concrete anchors. Do not drill into mortar joints! Be sure to mount in a solid

part of the block, generally 1" (25 mm) minimum from the side of the block. Cinder block must meet ASTM C-90 specifica-

tions. It is suggested that a standard electric drill on slow setting is used to drill the hole instead of a hammer drill to avoid

breaking out the back of the hole when entering a void or cavity.

• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.
• Make sure that the wall will safely support four times the combined load of the equipment and all attached hardware and

components.

WARNING

1

Place lock down plate (

A) on wall as a template. Level,

and mark the center of the two mounting holes.

Drill two 5/16" (8 mm) dia. holes to a minimum depth of

2.5" (64 mm). Insert anchors (

E) in holes flush with wall

as shown. Secure using two #14 x 2.5" wood screws (

C)

as shown in figure 1.4.

Figure. 1.4

CUT

AW

AY

VIEW

INCORRECT

CORRECT

wall

plate

wall

plate

plaster/

dry wall

plaster/

dry wall

concrete

concrete

1

3

2

E

Drill holes and insert anchors (

E).

Place lock down plate (

A) over anchors (E) and secure with

screws (

C).

Tighten all fasteners.

A

E

C

concrete

surface

• Tighten screws so that wall plate is firmly attached,

but do not overtighten. Overtightening can damage

screws, greatly reducing their holding power.

• Never tighten in excess of 80 in. • lb (9 N.M.).
• Always attach concrete expansion anchors directly

to load-bearing concrete.

• Never attach concrete expansion anchors to

concrete covered with plaster, drywall, or other

finishing material. If mounting to concrete surfaces

covered with a finishing surface is unavoidable,

the finishing surface must be counterbored as

shown below. Be sure concrete anchors do not

pull away from concrete when tightening screws. If

plaster/drywall is thicker than 5/8" (16 mm), custom

fasteners must be supplied by installer.

WARNING

A

C

E

PlayStation

®

3

Advertising