Industrial power supplies – Powersolve PDN100 Series User Manual
Page 3
Advertising
Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. England
Tel: 01635 521858 Fax: 01635 523771 Email: [email protected]
www.powersolve.co.uk
Industrial Power Supplies
Application of DC OK Active Signal (PDN10, PDN20)
De-rating Curves
DC OK
DC OK
DC OK
-V
-V
-V
5.1V
Relay
R
R
(a) 5V Signa
l
(b) LED
(c) Relay
Model
R
12V
≥1.5KΩ
15V
≥2KΩ
24V
≥3.9KΩ
Model
R
12V
≥2.4KΩ
15V
≥3KΩ
24V
≥4.7KΩ
Model Coil R
12V
≥700Ω
15V
≥700Ω
24V
≥1.2KΩ
DC OK Relay Contact (PDN40, PDN60, PDN100)
Contact Closed
When the output voltage reaches the adjusted output voltage
Contact Open
When the output voltage drops below 90% of the adjusted output voltage
Contact Rating (max.)
24V / 1A resistive load