Caution – Aqua-Pure MCA2001M User Manual

Page 8

Advertising
background image

Step 1

Shut off all water at main supply. On a private well system, turn off power to pump and drain pressure tank. Make certain pressure is relieved from
complete system by opening nearest faucet to drain system.

CAUTION

CAUTION

To reduce the risk associated with property damage due to water leakage:

• When water supply is shut off, shut off fuel or electric power to water heater.

Step 2

Cut main supply line as required to fi t Hydro-Charger in plumbing between well pump and pressure tank (Hydro-Charger may be installed in a vertical
or horizontal position). The Hydro-Charger has been supplied with both 1” threaded
and 1” barbed (insert) fi ttings to allow for installation with various types of piping
materials. When using the threaded nipples, use thread tape only. When using barbed
(insert) fi ttings, appropriate pipe clamps must be used. Once installed, the quick re-
lease nipples allow the Hydro-Charger to be rotated, so the air draw adjustment screw
is accessible for adjustment by a small bladed screwdriver. Allow at least 10 inches of
straight run of 1” pipe on both inlet and outlet side of the Hydro-Charger. Refer to Fig-
ure 2 for correct assembly. The quick release nipples also acts as a union to facilitate
the Hydro-Charger removal, inspection and cleaning as needed. With an installation on
PVC pipe and copper tubing it may require the addition of a normal plumbing union to
aid in removal from the plumbing due to the rigidity of that type of material. Make cer-
tain the directional arrows on the Hydro-Charger points toward the pressure tank and
the pressure control switch is located on the pressure tank side of Hydro-Charger as
in Figure 1. Rapid cycling of pump may occur if the pressure control switch is located
on well side. If a check valve is located between Hydro-Charger and pressure tank,
it may prevent the Hydro-Charger from performing properly. Relocate to well side of
Hydro-Charger.

Step 3

Turn back on the power to the well pump and pressurize the water lines to allow for adjustment of the Hydro-Charger. Check for leaks and adjust as
necessary.

IMPORTANT NOTES

IMPORTANT NOTES

• Do not apply heat near Hydro-Charger, as damage may occur. On badly scaled, older plumbing systems, it may be advantageous to install a WYE

Strainer to help prevent plugging of the Hydro-Charger nozzle with scale or debris. The use of a WYE Strainer must precede the Hydro-charger
on the inlet side by a minimum of 10”.

• If existing water system includes a captive-air type pressure tank (bladder) and it is desirable to install an additional air to water type with an air

release (not as a split steam type installation) install an air to water type pressure tank between the Hydro-Charger and the existing captive air
type pressure tank.

• Before proceeding with Hydro-Charger installed, re-verify adequate pumping rate pumping by following the procedure described in Section

2. After verifi cation of adequate fl ow, depressurize system as described previously.

• If installation is to be split streamed prior to fi lter vessel or is a public water supply see Figure 1, or refer to Special Instructions on page 3-5.

Step 4

Set Hydro-Charger by following these steps:

a)

Open nearest faucet until well pump starts, then close faucet.

b)

Place a fi nger lightly over the suction port (Figure 3). A slight suction should be de-
tected for approximately one third (1/3) of pumping cycle time. (Do not confuse with
one third (1/3) of pressure range).

c)

If suction is too short, increase by turning air adjustment screw (Figure 3), clockwise.
To decrease duration, turn counterclockwise.

d)

Repeat steps (a) through (c) until proper setting is obtained. The optimum cycle time
is 60 seconds or more, with an air draw of 20 seconds minimum.

IMPORTANT NOTE

IMPORTANT NOTE

When the duration of the suction is too long, the cold water may have a milky appearance caused by excess air in the water system. Cor-
rect this condition by reducing the duration of suction. This condition is commonly associated with bladder type pressure tanks. In extreme
cases where elimination of excess air prevents system from performing satisfactorily, it may be necessary to install an air to water pressure
tank with an air release valve.

3-2

Figure 2: HYDRO-CHARGER INSTALLATION

Figure 3

Advertising