Car2548fp series rectifier, Data sheet, Alarm table – GE Industrial Solutions CAR2548FP series User Manual
Page 13: Outline drawing
GE
Data Sheet
CAR2548FP series rectifier
Input: 90Vac to 264Vac; Output: 48Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A
March 28, 2013
©2013 General Electric Company. All rights reserved.
Page 13
Alarm Table
Test Condition
LED Indicator
Monitoring Signals
AC OK
DC OK
FAULT
FAULT
DC OK
AC OK
TEMP OK
1 Normal
Operation
Green
Green
OFF High High High High
2
Low or NO INPUT
OFF
OFF
Red
Low Low Low High
3 OVP
Green
OFF
Red
Low Low High High
4 Over
Current
Green
OFF
Red
Low Low High High
5
Over Temp Fault
Green
OFF
Red
Low Low High Low
Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no AC.
Outline Drawing
14.25 ±.020
4.000
±.020
.33
LATCH
POT ADJ.
POT ADJ.
2X
40X28mm FANS
.100
.060
1.610
±.020
14.69
HANDLE
CAPTIVE SCREW
RAF P/N 369
AIR FLOW
1.610
BEZEL
4.000
BEZEL
GREEN LED (AC OK)
GREEN LED (DC OK)
RED LED (FAULT)
TEST
CONNECTOR
POWER PIN P1
1.879
±.015
SIGNAL A1
.528 ±.015