Car2548fp series rectifier, Data sheet, Alarm table – GE Industrial Solutions CAR2548FP series User Manual

Page 13: Outline drawing

Advertising
background image

GE

Data Sheet

CAR2548FP series rectifier

Input: 90Vac to 264Vac; Output: 48Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A

March 28, 2013

©2013 General Electric Company. All rights reserved.

Page 13

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

AC OK

DC OK

FAULT

FAULT

DC OK

AC OK

TEMP OK

1 Normal

Operation

Green

Green

OFF High High High High

2

Low or NO INPUT

OFF

OFF

Red

Low Low Low High

3 OVP

Green

OFF

Red

Low Low High High

4 Over

Current

Green

OFF

Red

Low Low High High

5

Over Temp Fault

Green

OFF

Red

Low Low High Low

Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no AC.

Outline Drawing

14.25 ±.020

4.000

±.020

.33

LATCH

POT ADJ.

POT ADJ.

2X

40X28mm FANS

.100
.060

1.610
±.020

14.69

HANDLE

CAPTIVE SCREW

RAF P/N 369

AIR FLOW

1.610
BEZEL

4.000
BEZEL

GREEN LED (AC OK)

GREEN LED (DC OK)

RED LED (FAULT)

TEST

CONNECTOR

POWER PIN P1

1.879
±.015

SIGNAL A1

.528 ±.015