Car2512fp series rectifier, Data sheet, Absolute maximum ratings – GE Industrial Solutions CAR2548FP series User Manual

Page 2: Electrical specifications

Advertising
background image

GE

Data Sheet

CAR2512FP series rectifier

Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A

March 28, 2013

©2013 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional

operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Symbol

Min

Max

Unit

Input Voltage: Continuous

VIN

0

264

V

ac

Operating Ambient Temperature

TA

-10

70

1

°C

Storage Temperature

Tstg

-40

85

°C

I/O Isolation voltage to Frame (100% factory Hi-Pot tested)

1500

V

ac

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.

INPUT

Parameter

Symbol

Min

Typ

Max

Unit

Operational Range

V

IN

90

110/230

264 V

ac

Frequency Range

F

IN

47 50/60 63 Hz

Main Output Turn_OFF

V

IN

80

V

ac

Maximum Input Current, (V

IN

= 180Vac, V

O

= V

O, set

, I

O

=I

O, max

) I

IN

16

A

ac

Cold Start Inrush Current

I

IN

50

A

peak

(Excluding x-caps, 25C, <10ms, per ETSI 300-132)

Efficiency, (T

amb

=25C, V

in

= 230Vac, V

out

= 48Vdc, I

O

=I

O, max

)

92

%

Power Factor, (Vin=230Vac, I

O

=I

O, max

) PF

0.99

Holdup time, (Vin= 230Vac, Vout= 48Vdc, Tamb 25C,

I

O

=I

O, max

)

T 16.8 ms

Early warning prior to loss of DC output below regulation

2

ms

Ride through

T

8.3

ms

Leakage Current, (Vin= 250Vac, Fin = 60Hz)

I

IN

3

mArms

Isolation Input/Output

3000 V

ac

Input/Frame

1500

V

ac

Output/Frame

100

V

dc

48V

dc

MAIN OUTPUT

Parameter

Symbol

Min

Typ

Max

Unit

Output Power High Line Operation (180 – 264 Vac)

W

0 - 2500

W

Low Line Operation: 99Vac [Z03A/Z01A]
90 – 98 Vac [Z03A/Z01A]

0
0

-

1300/1000
1200/1000

W

Set point

V

out

47.95 48.00 48.05 V

dc

Overall regulation (load, temperature, aging)

-3

+3

%

Ripple and noise

2

540

mV

p-p

Turn-ON overshoot

+3

%

Turn-ON delay

T

2

sec

Remote ON/OFF delay time

40

ms

Turn-ON rise time (10 – 90% of V

out

)

50

ms

1

Derated above 50C at 2.5%/C

2

Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth

Advertising